Our Neutral Grounding Resistors Have Successfully Passed New Type Tests!
We had the type tests of our NEUTRAL GROUNDING RESISTORS performed at the VEIKI-VNL Accredited Laboratory, one of the leading test centers in Europe, located in Hungary. While all of our products passed the tests, it was confirmed that our products were produced in accordance with the current TEİAŞ specifications.
Our tests were applied to Neutral Grounding Resistance of 36/√3 kV 1000 A, 20 ohms for 10 seconds.
Tests Performed
1 | Degrees of Protection Provided by Enclosure (IP Test) | IP 23 | IEC 60259 : 2013 | Clause 12.2 / 13.2 / 14.2.3 b) Madde 12.2 / 13.2 / 14.2.3 b) |
TEİAŞ-MYD_2016-036.2 | Clause 3.1.1 Madde 3.1.1 |
2 | DC Resistance Measurement | 20 ohm ± 5% @ 20 °C | IEEE C57.32 : 2015 & IEEE C57.32a : 2020 | Clause 7.8 Madde 7.8 |
TEİAŞ-MYD_2016-036.2 | Clause 3.1.2 Madde 3.1.2 |
3 | Impedance Measurement @ 50 Hz | – | IEEE C57.32 : 2015 & IEEE C57.32a : 2020 | Annex A3 Ek A3 |
TEİAŞ-MYD_2016-036.2 | Clause 3.2.1 Madde 3.2.1 |
4 | Temperature Rise Test | a) 40 A continuous @ 50 Hz (40 A Sürekli) b) 1000 A 10 second @ 50 Hz (1000 A 10 s) |
IEEE C57.32 : 2020 | Clause 7.7 Madde 7.7 |
TEİAŞ-MYD_2016-036.2 | Clause 3.1.4 Madde 3.1.4 |
5 | Applied Voltage Test | a) 50 kV 1 min. 50 Hz (Direnç ile Kabin arası) b) 6 kV 1 min. 50 Hz (Direnç ile Blok arası) |
IEEE C57.32 : 2015 & IEEE C57.32a : 2020 | Clause 7.9.2 Madde 7.9.2 |
TEİAŞ-MYD_2016-036.2 | Clause 3.1.3.2 Madde 3.1.3.2 |