CTS 30 Changeover Module is the equipment that enables to select the convenient one between two different sources feeding the isolated power panel and transfer it to the output.

Advantages

  • Transfer Time: 40 ms
  • Communicates with the Remote Alarm Indicator and the Local Alarm Panel with the Modbus RTU protocol.

Applications Areas

It is used in Isolated Power Panels used in the electrical supply of Group 2 rooms in Medical Facilities (Hospitals, Health Centers, Dental Clinics, Aesthetic Centers, Animal Hospitals):

Group 2 rooms:

  • Anesthetic rooms
  • Operating rooms
  • Operation preparation rooms
  • Recovery room
  • Cardiac catheterization rooms
  • Intensive care units
  • Angiographic examination rooms

Standards

  • IEC 60947-5-1
  • IEC 60364-7-710

Technical Specification

Supply Voltage 220 Vac
Frequency 50/60 Hz
Power Consumption 5,5 W
Transfer Time ≤40 ms
Utilization Category AC-15
Insulation Measurement Uncertainty 11,5 mm ± 0,3
Ui 690 V
Uimp 4,0 kV

 

Type Size Download Link
MED - Isolated Power System PDF 1 MB Download
MED - Insulation Monitoring Devices PDF 1 MB Download
×
img