The EDS 30 Insulation Fault Detection Device is designed to locate insulation faults in IT systems.
The EDS 30 Insulation Fault Detection Device communicates with the Insulation Monitoring Device (IMD30) via the ModBus RTU protocol and quickly identifies which line is causing the fault. It continuously scans six current transformers, and if a leakage is detected, the alarm LED of the faulty channel lights up. Alarm details are displayed on the Local Alarm Panel (LAP70) and the Central Alarm Panel (RAI70).
Advantages
- Elegantly designed to locate insulation faults in IT systems
- Number of channels: 6
- Remote insulation testing and fault contact outputs
Applications Areas
Used in Isolated Power Panels supplying Group 2 rooms in medical facilities such as hospitals, health centers, dental clinics, aesthetic centers, and veterinary hospitals.
Group 2 rooms include:
- Anesthetic rooms
- Operating rooms
- Pre-operative rooms
- Recovery room
- Cardiac catheterization rooms
- Intensive care units
- Angiographic examination rooms
Standards
- IEC 61557-9
- IEC 60364-7-710
|
Technical Specification |
|
| Supply Voltage | 24 Vac/dc |
| Frequency | 50/60 Hz |
| Power Consumption | 1,5 W |
| Number of Channels | 6 |
| CT Inner Diameter | ≤ 1 kΩ |
| Insulation Measurement Uncertainty | 11,5 mm ± 0,3 |
| Response Time | ≤ 2 s |
| Response Value | <0,5 mA |