Isolated power panels are used in group 2 rooms in medical locations, and they consist of auxiliary devices and test combinations such as isolated transformer, insulation monitoring device and insulation fault location devices.

In the IT system different from TN and TT systems, when an insulation failure occurs, IT systems ensures that there is no electrical problem by preventing the circuit breakers from tripping and interrupting the system. The medical equipment continues to function, the fault currents are reduced to non-critical values, and the energy interruption is prevented.

Insulation level is continuously monitored by the isolated power panels and if a value less than 50 kΩ is detected alarm is created and logged. Aforementioned alarm can also be displayed through the control panel in the operating rooms and local and remote alarm panels.

Isolated power panels, which have a fault location detection system, have the feature of detecting in which line the insulation fault occurred. Thanks to this feature, the time to detect the location of the insulation fault is reduced.

The following medical locations that carrying vital importance in hospitals and where medical devices are directly connected to patients are defined as group 2 room in accordance with IEC 60364-7-710 standard and isolated power systems are used in these rooms.

 

Advantages

  • Compact size
  • Option up to 24 outgoing

Application Areas

Used in the electrical supply of Group 2 rooms in Medical Facilities (Hospitals, Health Centers, Dental Clinics, Aesthetic Centers, Animal Hospitals):

  • Anesthetic rooms
  • Operating rooms
  • Operation preparation rooms
  • Recovery room
  • Cardiac catheterization rooms
  • Intensive care units
  • Angiographic examination rooms

Standards

  • IEC 60364-7-710

Dimensions

  • (WxDxH) 405 x 405 x 1700 mm
IGP IGT IGD IGH
Power Supply - Main
- Safety
OK
-
OK
OK
OK
-
OK
OK
Insulation Monitoring Device OK OK OK OK
Changeover Module - OK - OK
Insulation Fault Location Device - - OK OK
Alarm Outputs - Insulation Fault
- Over Load
- Over Temperature
- Switchover Failure
- Insulation Fault Location
OK
OK
OK
-
-
OK
OK
OK
OK
-
OK
OK
OK
-
OK
OK
OK
OK
OK
OK
Rated Power 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA
Rated Voltage - Main
- Safety
230 Vac
-
230 Vac
230 Vac
230 Vac
-
230 Vac
230 Vac
Rated Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Rated Insulation Level 3 kV / 1 min 3 kV / 1 min 3 kV / 1 min 3 kV / 1 min
Leakage Current to Enclosure < 0.5 mA < 0.5 mA < 0.5 mA < 0.5 mA
Response Range 50 … 750 kΩ 50 … 750 kΩ 50 … 750 kΩ 50 … 750 kΩ
Fault Detection Responce Time < 2 s < 2 s < 2 s < 2 s
Switchover Time - < 200 ms - < 200 ms
Operating Temperature  -5 … 50 °C  -5 … 50 °C  -5 … 50 °C  -5 … 50 °C
Storage Temperature  -25 … 60 °C  -25 … 60 °C  -25 … 60 °C  -25 … 60 °C
Cooling System Natural Natural Natural Natural
Protection Class IP 31 IP 31 IP 31 IP 31
Distribution Outgoings 6 … 24 6 … 24 6 … 24 6 … 24
Color - Door
- Side cover
RAL 9003
RAL 7015
RAL 9003
RAL 7015
RAL 9003
RAL 7015
RAL 9003
RAL 7015
Standards IEC 60364-7-710 IEC 60364-7-710 IEC 60364-7-710 IEC 60364-7-710
Type Size Download Link
IG - Medical Isolated Power Panels PDF 1 MB Download
×
img